Spacing in Metres on Emergency Escape Routes
Notes: These tables are based on the following factors; Light output ratios measured to BS5225 and lamp lumen outputs are from GE Lighting Warm white lamps.

Requirements from BS5266/EN1838
Permanently unobstructed escape routes:

Require minimum of 0.2 lux along the centre line of the escape route, where there is a possibility of an obstruction occuring along the route 1lux minimum is required.

Undefined, Open areas:
The minimum level of illumination required throughout the area is 0.5 lux excluding a half metre border around the edge of the room which can be at a lower level.