HIGH POWER DC SYSTEMS - SLA/SLG RANGE

Emergency Lighting Kits to Operate 12 Volt Tungsten Halogen Lamps in the Event of a Power Failure

DC's high power systems are manufactured to the highest standards from the UK's leading systems supplier. They offer long trouble free operation with a wide choice of batteries and options for specific applications.
Features
  • NM, M single or dual output versions for optimum system flexibility
  • Lift off cubicle covers provide easy access for maintenance
  • Separate battery and gear compartments for safer operation
  • Cubicles are manufactured from sheet steel and are epoxy powder coated for a long life in RAL-7032
  • Choice of Contactors to BS5424 as standard, BS764 types available.
  • A wide battery choice to give optimum flexibility
  • A range of pre-engineered options to allow complete control and monitoring

SLA - Valve regulated Lead Acid (VR) range, Design Life In Excess of 4-7 Years BS 6745
System Nominal Range
Model Designation
Power Rating (W) 1 hour
Power Rating (W) 2 hours
Power Rating (W) 3 hours
Battery Capacity Ah
Cabinet Type
24 Volts
12 Cells
SLA/24/22/*VR
340
195
35
22
F1
SLA/24/30/*VR
480
280
190
30
F1
SLA/24/46/*VR
750
430
300
46
F1
SLA/24/68/*VR
1050
610
420
68
F1
SLA/24/84/*VR
1350
790
545
84
F1
SLA/24/98/*VR
1550
925
635
98
F1
SLA/24/120/*VR
1925
1120
780
120
F1
50 Volts
24 Cells
SLA/50/22/*VR
680
390
270
22
F1
SLA/50/30/*VR
960
560
380
30
F1
SLA/50/46/*VR
1500
860
600
46
F1
SLA/50/68/*VR
2100
1220
840
68
F1
SLA/50/84/*VR
2700
1580
1090
84
F2
SLA/50/98/*VR
3150
1850
1270
98
F2
SLA/50/120/*VR
3850
2250
1560
120
F2
SLA/50/152/*VR
4700
2800
1960
152
F3
110 Volts
54 Cells
SLA/110/22/*VR
1500
890
610
22
F2
SLA/110/30/*VR
2150
1250
870
30
F2
SLA/110/46/*VR
3350
1950
1350
46
F2
SLA/110/68/*VR
4800
2750
1900
68
F3
SLA/110/84/*VR
6100
3550
2450
84
F3
SLA/110/98/*VR
7150
4150
2850
98
(2)F4
SLA/110/120/*VR
8700
5050
3500
120
(2)F4
*Model part codes
To select a model in the SLA range, insert either NM or M describing the system operation and the system duration 1,2 or 3 hours. Options required should be specified using the relevant suffix e.g. "/LE" = Low electrolyte alarm, e.g. SLA/110/ 46/M3VR/LE is a 110V Maintained system supplying 1350 watts for 3 hours via its Valve Regulated, lead acid battery and has a Low electrolyte alarm facility.

 

SLG - Valve regulated Lead Acid (VR) range, Design Life of 10 Years BS 6290 PT.4
System Nominal Range
Model Designation
Power Rating (W) 1 hour
Power Rating (W) 2 hours
Power Rating (W) 3 hours
Battery Capacity Ah
Cabinet Type
24 Volts
12 Cells
SLG/24/30/*VR
340
195
35
22
F1
SLG/24/30/*VR
480
280
190
30
F1
SLG/24/46/*VR
750
430
300
46
F1
SLG/24/68/*VR
1050
610
420
68
F1
SLG/24/84/*VR
1350
790
545
84
F1
SLG/24/98/*VR
1550
925
635
98
F1
SLG/24/120/*VR
1925
1120
780
120
F1
50 Volts
24 Cells
SLG/50/22/*VR
680
390
270
22
F1
SLG/50/30/*VR
960
560
380
30
F1
SLG/50/46/*VR
1500
860
600
46
F1
SLG/50/68/*VR
2100
1220
840
68
F1
SLG/50/84/*VR
2700
1580
1090
84
F2
SLG/50/98/*VR
3150
1850
1270
98
F2
SLG/50/120/*VR
3850
2250
1560
120
F2
SLG/50/152/*VR
4700
2800
1960
152
F3
110 Volts
54 Cells
SLG/110/22/*VR
1500
890
610
22
F2
SLG/110/30/*VR
2150
1250
870
30
F2
SLG/110/46/*VR
3350
1950
1350
46
F2
SLG/110/68/*VR
4800
2750
1900
68
F3
SLG/110/84/*VR
6100
3550
2450
84
F3
SLG/110/98/*VR
7150
4150
2850
98
(2)F4
SLG/110/120/*VR
8700
5050
3500
120
(2)F4
*Model part codes
To select a model in the SLG range, insert either NM or M describing the system operation and the system duration 1,2 or 3 hours. Options required should be specified using the relevant suffix e.g. "/LE" = Low electrolyte alarm, e.g. SLG/110/ 46/M3VR/LE is a 110V Maintained system supplying 1350 watts for 3 hours via its Valve Regulated, lead acid battery and has a Low electrolyte alarm facility.

Cabinet sizes (millimetres)
F1 Height 1000 x Length 600 x Depth 440
F2 Height 1250 x Length 800 x Depth 540
F3 Height 1250 x Length 1000 x Depth 640
F4 1 x Height 1250 x Length 600 x Depth 640 + 1 x Height 1250 x Length 800 x Depth 640

Standard Options
DC Emergency Systems Limited have selected a number of popular options that are pre-engineered to accompany any system, these are included below with their designations:
BS764 contactor
MCB on input
Low voltage disconnect
MCB on M circuit
Digital Voltmeter/ammeter
Maintained control relay
Earth fault monitor
Night watchman's switch
Engineer's test key
3 phase monitor
Fire alarm relay
Solar dial time switch
High/low volts monitor
Remote alarm unit
Low electrolyte alarm
Sub-circuit relay
Double pole fused output(s)
/BS
/MI
/LVD
/MM
/DM
/MR
/EF
/NW
/ET
/PF
/FA
/TS
/HL
/RA
/LE
/SR
/XD
(X should be replaced with the number of outputs required).
Low Voltage disconnection is standard with the VR battery range.

The SLA / SLG range is available with alternative battery types (PL= Plante, FP=Flat Plate and NC=Nickel Cadmium), please consult our sales office for relevant ratings and cubicle sizes.

Specification
Input voltage: 230V +10-6%, 50Hz, 1 phase or 380/415V 50Hz (3 phase input is fitted with 3 phase monitoring as standard) Alternative inputs are available please consult DC for details.
Charger: Thyristor controlled constant voltage charger with an electronic current limit.
Protection: Short circuit, low battery voltage and reverse battery connection.
Recharge time: 80% within 14 hours, full recharge within 24 hours.
End of discharge: Battery voltage not less than 85% of rated nominal (BS5266).
Fuses: Industrial HRC fuses complying with requirements of BS88 Part 2:1975.
Contactors: To BS5424 as standard, BS764 types available.
Indicators: Standard on all units: mains healthy neon, charge fail LED, charge ammeter, battery voltmeter.