| LOW POWER DC SYSTEMS - SLA ECONOMY RANGE |

| DC Emergency Systems Ltd offer the Economy
range of lower power systems, using sealed recombination lead acid batteries.
The SLA uses the 5-year design life battery. Tables below show the standard ranges but these can be augmented with alternative batteries and durations if required. |
| SLA Economy Range |
|
Model*
|
Power
Rating
(W) for 1 hour |
Power
Rating
(W) for 3 hours |
Nominal
Output Voltage
|
Cabinet
Type
|
| SLA/12/15 |
140
|
55
|
12
|
W1
|
| SLA/24/6 |
84
|
38
|
24
|
W1
|
| SLA/24/15 |
216
|
90
|
24
|
W1
|
| SLA/24/24 |
300
|
150
|
24
|
W2
|
| SLA/24/38 |
480
|
234
|
24
|
W2
|
| SLA/24/48 |
550
|
300
|
24
|
W2
|
| SLA/24/65 |
960
|
432
|
24
|
W2
|
*Specify NM,M operation and duration required (i.e. NM3) e.g. SLA/12/15/NM1 = 12V 140 watts Non Maintained operation for 1 hour. Battery rated to 1.7 v.p.c at 20 degrees C Ambient Temperature. Complying with BS6290 Part 4 |
|
Cubicle
sizes (millimetres) Recharge Time: Chargers rated to provide
80% recharge within 14 hours and full charge in 24 hours following a full
rated discharge as defined in BS5266 Contactors: Mains failure Contactor to BS5424 Part 1 fitted as standard equipment. Contactor to BS764 are available upon request at extra cost (Cubicle sizes will vary with this option. Load: Standard ratings as shown in the performance table. For loads in excess of those shown please refer to manufacturer. Fuse gear: Comply with the general requirements of BS88 Part 2; 1975 mainly being of the industrial H.R.C type in withdrawable carriers. Low Volts Disconnect: Is included to protect the battery against deep discharge caused by prolonged mains or cyclic power cuts. Cubicles: Fabricated from thick zinc coated mild steel of folded construction to provide maximum strength and rigidity. Paint finish is stove enamel epoxy gloss, which accommodates both the charging equipment and the batteries. Standard Controls: Neon indicated Mains on and off switch and battery voltage indicator. |